ABB ACS560 Firmware Manual page 183

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
10.15
DI6 ON delay
*DI status
**Delayed DI status
t
=
10.15 DI6 ON delay
On
t
=
10.16 DI6 OFF delay
Off
*Electrical status of digital input. Indicated by
**Indicated by
10.02 DI delayed
0.0 ... 3000.0 s
10.16
DI6 OFF delay
0.0 ... 3000.0 s
10.21
RO status
Bit
Value
0
1 = RO1 is energized.
1
1 = RO2 is energized.
2
1 = RO3 is energized.
3...15
Reserved
0b0000...0b1111
10.22
RO force selection
Bit
Value
0
1 = Force RO1 to value of bit 0 of parameter
1
1 = Force RO2 to value of bit 1 of parameter
2
1 = Force RO3 to value of bit 2 of parameter
3...15
Reserved
0b0000...0b1111
Description
Defines the activation delay for digital input DI6.
t
t
On
Off
10.01 DI
status.
Activation delay for DI6.
Defines the deactivation delay for digital input DI6. See
parameter
10.15 DI6 ON
Deactivation delay for DI6.
Status of relay outputs RO3...RO1.
Status of relay outputs.
The signals connected to the relay outputs can be overridden
for e.g. testing purposes. A bit in parameter
data
is provided for each relay output, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
10.22
and 10.23).
Override selection for relay outputs.
t
On
status.
delay.
10.23 RO forced
10.23 RO forced
10.23 RO forced
10.23 RO forced
Parameters 183
Def/FbEq16
0.0 s
1
0
1
0
Time
t
Off
10 = 1 s
0.0 s
10 = 1 s
0b0000
1 = 1
0b0000
data. (0 = Normal mode)
data. (0 = Normal mode)
data. (0 = Normal mode)
1 = 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents