Limits - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
28.92
Frequency ref act 3
-500.00...500.00
Hz
28.96
Frequency ref act 7
-500.00...500.00
Hz
28.97
Frequency ref
unlimited
-500.00...500.00
Hz
30

30 Limits

30.01
Limit word 1
Bit
Name
0
Torq lim
1...2
Reserved
3
Torq ref max
4
Torq ref min
5
Tlim max speed
6
Tlim min speed
7
Max speed ref lim 1 = Speed reference is being limited by
8
Min speed ref lim 1 = Speed reference is being limited by
9
Max freq ref lim
10
Min freq ref lim
0b0000...0b1111
Description
Displays the frequency reference after the function applied by
parameter
28.13 Ext1 frequency function
selection
(19.11 Ext1/Ext2
diagram on page 486.
This parameter is read-only.
Frequency reference after selection.
Displays the frequency reference after application of constant
frequencies, control panel reference, etc. See the control
chain diagram on page 486.
This parameter is read-only.
Frequency reference 7.
Displays the frequency reference after application of critical
frequencies, but before ramping and limiting. See the control
chain diagram on page 486.
This parameter is read-only.
Frequency reference before ramping and limiting.
Drive operation limits.
Displays limit word 1.
This parameter is read-only.f
Description
1 = Drive torque is limited by the motor control (undervoltage control,
current control, load angle control or pull-out control), or by the torque
limits defined by parameters.
1 = Torque reference ramp input is being limited by
torque
ref,
30.20 Maximum torque
30.27 Power generating
1 = Torque reference ramp input is being limited by
torque
ref,
30.19 Minimum torque
30.27 Power generating
1 = Torque reference is being limited by the rush control because of
maximum speed limit
1 = Torque reference is being limited by the rush control because of
minimum speed limit
1 = Frequency reference is being limited by
1 = Frequency reference is being limited by
Limit word 1.
(if any), and after
selection). See the control chain
1,
30.26 Power motoring
limit. See the diagram on page 496.
1,
30.26 Power motoring
limit. See the diagram on page 496.
(30.12 Maximum
speed)
(30.11 Minimum
speed)
30.12 Maximum speed
30.11 Minimum speed
30.14 Maximum frequency
30.13 Minimum frequency
Parameters 251
Def/FbEq16
0.00
See par.
46.02
0.00
See par.
46.02
0.00
See par.
46.02
0b0000
26.09 Maximum
limit, or
26.08 Minimum
limit, or
1 = 1