Component
S120 Chassis
Basic Line Module
Smart Line Module
Active Interface Module
Active Interface Module
Active Interface Module
Active Line Module
Motor Module
G130
Power Module
Power Module
Power Module
1)
The clearances refer to the area around the ventilation slots on the front cover.
Air-flow guidance for S120 Smart Line Module,
Active Line Module, Motor Module, frame sizes FX, GX,
G130 frame size FX, GX
Ventilation concept for chassis power units
The cooling air is drawn in at the bottom of the power units. The warm outlet air must be dissipated via the top cover/
hood or via side openings in the cabinet at the level of the top of the device. No items of equipment which could
impede the flow of air may be mounted above the air outlet openings in the power blocks of a power unit.
General Engineering Information for SINAMICS
Frame size
Clearance front
[mm]
FB, GB
GX, HX, JX
FI
GI
HI, JI
FX, GX, HX, JX
FX, GX, HX, JX
FX
GX
HX, JX
1)
Clearance top
[mm]
40
250
40
250
40
250
50
250
40
250
40
250
40
250
40
250
50
250
40
250
Air-flow guidance for S120 Active Interface Module,
Active Line Module, Motor Module, frame sizes HX,JX,
Basic Line Module, frame sizes FB, GB,
G130 frame size HX
SINAMICS Engineering Manual - May 2008
Engineering Information
Clearance bottom
[mm]
150
150
150
150
0
150
150
150
150
150
159/396