SINAMICS S120 Cabinet Modules
Engineering Information

Option Y11 (Factory assembly of Cabinet Modules into transport units)

Cabinet Modules can be ordered as factory-assembled transport units with a maximum width of up to 2400 mm. This
option allows the modules to be assembled as quickly and simply as possible at their installation site.
The relevant modules are shipped as finished transport units which are interconnected both electrically and
mechanically. No additional wiring need be installed between the units on site. Please note that this does not apply to
the DRIVE-CLiQ connections between cabinets. These must be ordered separately as the customer's final
implementation requirements cannot be determined from the order.
When DC busbars (options M80 to M87) for these "units" are selected, it must be ensured that identical busbars are
installed within the transport unit and are compatible with all adjacent Cabinet Modules. Uninterrupted busbars are
used in transport units to facilitate handling. This must be taken into account with respect to auxiliary voltage
supplies. If the auxiliary voltage circuits are to be divided up, then separate transport units must be selected
accordingly.
In a transport unit order, all the Cabinet Modules included in the unit and their installation sequence from left to right
must be specified in plain text according to the syntax below:
Plain text required to order:
Transport unit
Serial number of transport unit
Position of Cabinet Module within transport unit
(from left to right)
Option Y11 is particularly recommended for units comprising Line Connection Modules and Line Modules because
the required precharging circuits and connection busbars, for example, can be incorporated in the transport unit for
certain variants. Please refer to the assignment tables in the section "Line Connection Modules".
Example:
SINAMICS Engineering Manual – May 2008
300/396
© Siemens AG
TE 1 - 1...6