SINAMICS S120 Chassis (Smart Line Modules), continued
Dimension drawing 5, frame size JX:
380 V to 480 V
500 V to 690 V
1000 – 1400 kW
Side view
Required clearance for ventilation - - - - - -
Line supply connection
Max. connection cross-
M12 screw
section
DIN
NEC, CEC
(No. of holes) DIN
VDE
AWG/MCM
mm²
6 x 240
6 x 500 MCM
630 – 800 kW
Rear view
DC link connection
Max. connection
cross-section
VDE
mm²
(3)
60 x 60 x 8
Dimension Drawings
Engineering Information
Grounding
Busbar
Max. connection cross-
connection
sectio
DIN
VDE
mm²
PE1
1 x 240
PE2
2 x 240
SINAMICS Engineering Manual - May 2008
M12 screw
NEC, CEC
(No. of holes)
AWG/MCM
1 x 500 MCM
(1)
2 x 500 MCM
(2)
351/396
© Siemens AG