Siemens SINAMICS G130 Engineering Manual page 362

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Dimension Drawings
Engineering Information
SINAMICS S120 Chassis (Motor Modules), continued
Dimension drawing 16, frame size HX:
380 V to 480 V
500 V to 690 V
Side view
Required clearance for ventilation - - - - - -
DC link connection
Max. connection cross-
Busbar
section
connection
DIN
VDE
mm²
60 x 60 x 5
SINAMICS Engineering Manual – May 2008
362/396
© Siemens AG
315 - 450 kW
400 - 560 kW
Rear view
Motor connection
Max. connection
cross-section
DIN
NEC, CEC
VDE
AWG/MCM
mm²
4 x 240
4 x 500
MCM
Grounding
M12 screw
Max. connection cross-
section
(No. of holes)
DIN
VDE
mm²
(2)
PE1
1 x 240
PE2
2 x 240
M12 screw
NEC, CEC
(No. of holes)
AWG/MCM
1 x 500 MCM
(1)
2 x 500 MCM
(2)