Siemens SINAMICS G130 Engineering Manual page 249

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Smart Line Modules
The auxiliary voltage for Smart Line Modules is connected via the auxiliary voltage busbar. The following components
require auxiliary power:
24 V DC:
Control electronics
400 V resp. 690 V AC: Power unit fans
Fuse protection down-circuit of the auxiliary voltage busbar is provided in the Cabinet Module.
Order No.
Frame
size
Supply voltage 380 V – 480 V 3AC (DC link voltage 500 V – 630 V)
6SL3730-6TE41-1AA0
HX
6SL3730-6TE41-1BA0
HX
6SL3730-6TE41-1BC0
HX
6SL3730-6TE41-3AA0
JX
6SL3730-6TE41-3BA0
JX
6SL3730-6TE41-3BC0
JX
6SL3730-6TE41-7AA0
JX
6SL3730-6TE41-7BA0
JX
6SL3730-6TE41-7BC0
JX
Supply voltage 500 V – 690 V 3AC (DC link voltage 650 V – 900 V)
6SL3730-6TG38-8AA0
HX
6SL3730-6TG38-8BA0
HX
6SL3730-6TG38-8BC0
HX
6SL3730-6TG41-2AA0
JX
6SL3730-6TG41-2BA0
JX
6SL3730-6TG41-2BC0
JX
6SL3730-6TG41-7AA0
JX
6SL3730-6TG41-7BA0
JX
6SL3730-6TG41-7BC0
JX
1)
Power requirement of Control electronics, auxiliary power supply for fans.
Rated rectifier/regenerative
power at 400 V resp. 690 V
[kW]
500
500
500
630
630
630
800
800
800
710
710
710
1000
1000
1000
1400
1400
1400
SINAMICS S120 Cabinet Modules
Engineering Information
Rated Input current
Current requirement
I
24 V DC
rated
[A]
[A]
883
1.4
883
1.4
883
1.4
1093
1.5
1093
1.5
1093
1.5
1430
1.7
1430
1.7
1430
1.7
757
1.4
757
1.4
757
1.4
1009
1.5
1009
1.5
1009
1.5
1430
1.7
1430
1.7
1430
1.7
SINAMICS Engineering Manual - May 2008
1)
400 V resp. 690V AC
50 Hz
60 Hz
[A]
[A]
3.2
In preparation
3.2
3.2
4.7
4.7
4.7
4.7
4.7
4.7
3.2
In preparation
3.2
3.2
4.7
4.7
4.7
4.7
4.7
4.7
249/396