Dc Link Fuses; Parallel Connections Of Basic Line Modules - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

DC link fuses

The Basic Line Modules do not have DC link fuses as standard.
If fuses are required, they can be ordered with option N52. The fuses are mounted on the connecting rail to the DC
busbar in the cabinet and not in the power unit itself.

Parallel connections of Basic Line Modules

Frame sizes GB/ GD are designed as a special variant which is also suitable for operation in parallel connections on
one Line Connection Module. Line-side fuses need to be provided to selectively protect the individual Basic Line
Modules in a parallel connection. The standard cabinet needs to be widened by 200 mm for this purpose. These units
can be identified by the "B" in the third to last position of the order number (example: 6SL3730-1T.41-.AA0 is the
variant without line-side fuses, 6SL3730-1T.41-.BA0 resp. 6SL3730-1T.41-.BC0 is the variant prepared for parallel
connection).
These units are installed to the right and left of the Line Connection Module. The design of the two variants is
identical. The Basic Line Module for mounting on the left of the LCM differs only in that it is provided with additional
connecting rails. The distinction between the left and right variants can be identified by the last but one position in the
order number, i.e. an "A" stands for the right-hand variant and a "C" for the left-hand variant.
Rated power at
Basic Line Modules
400 V
Order No.
[kW]
Supply voltage 380 V – 480 V 3AC (DC link voltage 510 – 650 V)
200
6SL3730-1TE34-2AA0
250
6SL3730-1TE35-3AA0
400
6SL3730-1TE38-2AA0
560
6SL3730-1TE41-2AA0
560
6SL3730-1TE41-2BA0
560
6SL3730-1TE41-2BC0
710
6SL3730-1TE41-5AA0
710
6SL3730-1TE41-5BA0
710
6SL3730-1TE41-5BC0
900
6SL3730-1TE41-8AA0
900
6SL3730-1TE41-8BA0
900
6SL3730-1TE41-8BC0
Rated power at
500 V resp. 690 V
[kW]
Supply voltage 500 V – 690 V 3AC (DC link voltage 675 – 930 V)
180 / 250
6SL3730-1TH33-0AA0
255 / 355
6SL3730-1TH34-3AA0
400 / 560
6SL3730-1TH36-8AA0
650 / 900
6SL3730-1TH41-1AA0
650 / 900
6SL3730-1TH41-1BA0
650 / 900
6SL3730-1TH41-1BC0
800 / 1100
6SL3730-1TH41-4AA0
800 / 1100
6SL3730-1TH41-4BA0
800 / 1100
6SL3730-1TH41-4BC0
1085 / 1500
6SL3730-1TH41-8AA0
1085 / 1500
6SL3730-1TH41-8BA0
1085 / 1500
6SL3730-1TH41-8BC0
Order number assignment for BLMs
Please note that only Basic Line Modules with exactly the same output power rating can be connected in parallel.
The potential for imbalances in current distribution means that current derating of 7.5 % must be applied and this
must be taken into account when the modules are dimensioned.
SINAMICS S120 Cabinet Modules
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
For parallel connection, mounted on right of LCM
For parallel connection, mounted on left of LCM
SINAMICS Engineering Manual - May 2008
Engineering Information
273/396
© Siemens AG

Hide quick links: