Siemens SINAMICS G130 Engineering Manual page 178

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS G130
Engineering Information
4.
The converter is controlled exclusively via the digital inputs/outputs or analog inputs/outputs on the optional
TM31 customer interface.
Terminal block on CU320
-X122
Factory setting
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Not assigned
M1
M1
DI/DO8
Not assigned
DI/DO9
Not assigned
M (GND)
DI/DO10
Not assigned
DI/DO11
Not assigned
M (GND)
-X132
DI4
Not assigned
DI5
Not assigned
DI6
Not assigned
DI7
Not assigned
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
Not assigned
M (GND)
DI/DO14
Not assigned
DI/DO15
Not assigned
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
Terminal block on TM31
Factory setting
-X520
Optocoupler inputs connected to common
potential
DI0
ON/OFF 1
DI1
Increase setpoint/fixed setpoint 0
DI2
Decrease setpoint/fixed setpoint 1
DI3
Acknowledge fault
-X530
Optocoupler inputs connected to common
potential
DI4
OFF 2
DI5
OFF 3
DI6
External fault
DI7
-X541
Bidirectional inputs/outputs
DI/DO8
Message: Ready to start
DI/DO9
Not assigned
1)
A jumper must be inserted here if these inputs are not used
SINAMICS Engineering Manual – May 2008
178/396
© Siemens AG
1)
1)
1)
Comment
Factory-set as output
Factory-set as output
Factory-set as output
Factory-set as output
Output is used (reserved) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output
Comment
Parameters can be set in the firmware to determine whether
operation is via motorized digital potentiometer or fixed
setpoint
Immediate pulse disable, motor coasts to standstill
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Factory-set as input

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150

Table of Contents