The converter is controlled exclusively via the standard digital inputs/outputs on the Control Unit.
Terminal block on CU320
-X122
Factory setting
DI0
ON/OFF 1
DI1
Increase setpoint/fixed setpoint 0
DI2
Decrease setpoint/fixed setpoint 1
DI3
Acknowledge fault
M1
M1
DI/DO8
Inverter enable (Run)
DI/DO9
No fault
M (GND)
DI/DO10
P24
DI/DO11
External alarm
M (GND)
-X132
DI4
OFF 2
DI5
OFF 3
DI6
External fault 1
DI7
Not assigned
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
P24
M (GND)
DI/DO14
P24
DI/DO15
P24
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used
1)
1)
1)
1)
Engineering Information
Comment
Parameters can be set in the firmware to determine whether
operation is via motorized digital potentiometer or fixed
setpoint.
Factory-set as output
Low active
Immediate pulse disable, motor coasts to standstill
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Output is used (reserved) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output
SINAMICS Engineering Manual - May 2008
© Siemens AG
SINAMICS G130
175/396