Sent Transmission Options Per Trend Channel - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Send test e-mail to
receiver
Note
Set transmit interval
128 / 176
Siemens
Building Technologies
You can send a test e-mail to the receiver to ensure the settings are correct.
1. Click Test receiver or the red pencil symbol .
2. In the Edit window, select the Trigger option.
3. Confirm with OK.
OZW sends a test e-mail to the entered receiver and confirms the
transmission under the data point Trend data sent with Yes.
If transmission failed, a possible cause is provided under Reason, see
Section 2.7, Functional check, "Test message receiver".
4. Check whether the e-mail arrived at the receiver.
E-mail receiver settings are retained when deleting or overwriting an existing trend
definition.
9.3.2

Sent transmission options per trend channel

The transmit interval can be set separately for each trend channel 1...5.
1. In secondary navigation, select desired Trend channel 1...5.
The window displays name, state, circular logging, transmit interval, and
message receiver.
1. Click Transmit interval or click the red pencil
The edit window opens.
Web server OZW772... V6.0
Trend functions
.
CE1C5701en
2015-10-12