Fault indication
Notes
No fault
Fault
Final steps
Note
42 / 176
Siemens
Building Technologies
2.9
Final steps
2.9.1
Check faults
The fault indicator displays the plant state.
No faults may be pending after commissioning. Additional information on faults is
available in Section 4.3.
The fault indicator remains green as long as no fault is pending.
The fault indicator changes to red for faults. The most severe plant faults are
displayed.
· Device name
· Fault text
2.9.2
Final steps on Web Server
The final function checks are conducted on the Web Server, the cover is mounted
and the LEDs checked.
On display and operating elements, see Section 1.2.
Procedure:
1.
Unplug USB cable.
2.
Switch off message inhibition and address mode.
– Switch 8 must be set to "Off"
– Address mode LED
3.
Mount terminal cover.
4.
Press Remote
button for more than 6 seconds.
– The Web Server sends a system report to the defined message receivers.
– Fault LED
displays (flashing) error in establishing communications.
5.
LED On
must be steady green.
6.
Fault LED
must be off.
Web server OZW772... V6.0
Commissioning
must be off.
CE1C5701en
2015-10-12