Test condition
LAN
Internet
Access via portal
Access without portal
Test message receiver
Note
Siemens
Building Technologies
2.7

Functional check

Connections must be tested if all settings were made to the Web Server as well as
to KNX devices.
A PC on the local network is used to test operations via LAN. The log in dialog box
must appear after entering the local IP address for the Web Server (see Section
2.2.2).
We recommend using mobile participants with Internet access (Smart phone,
mobile phone) to test operation over the Internet. The log in dialog box must
appear after entering the public IP address or plant domain.
Access via portal must be possible after registration, log on, and plant activations
(see Section 3.1 "Set up access via portal").
The log in dialog box displays after entering the public IP address of plant domain
(see Section 4 "Operate using a web browser").
Do the test if the Web Server is to send a message or system report via e-mail
for a fault.
· The test is also carried out if message inhibition is switched on.
Path: Home > 0.2.150 OZW772.xx > Settings > Message receiver
Data point
Test message receiver
Default val: ---
Setting val: Message receiver 1..4
System report sent
Display val: ---, Yes, No
Cause
Display val:
---, Network cable, DNS setting,
Address mail server, Port number
mail server, E-mail address
receiver, Authentication mail server
See the following table.
Message inhibition
Display values: Yes, No
Web server OZW772... V6.0
Commissioning
Explanation, example
Select a message receiver to test the
connection to the receiver.
The display changes from "
seconds to:
"Yes":
Message sent successfully
"No":
Message receiver not reached
"Cause" displays the results of "System
report sent".
For "Yes" the cause is "---".
For "No" the cause is displayed.
The first cause is displayed for multiple faults.
Shows the message suppression switch
setting (8) (see Section 1.2).
" after a few
---
39 / 176