11.3.4 Alternative network configuration

We recommend setting up IP settings for commissioning as an alternative
configuration if a PC, connected to a network, is temporarily used to commission
the Web Server and the local area network.
On the PC, set as follows:
1.
Select Start > Control Panel > Network connections > Local Area Connection.
2.
Select the "General" tab.
3.
Click [ Properties ]
4.
Select "Internet Protocol (TCP/IP)".
5.
Click [ Properties ]
6.
Select "Alternate Configuration" tab.
7.
Enter IP address, subnet mark and operational standard gateway
as well as DNS server.
The PC assumes the configuration with these settings as soon as it is
no longer integrated in the standard network.
Web server OZW772... V6.0
Appendix
CE1C5701en
2015-10-12