Notes
Note
Comfort heating
setpoint
Note
Comfort cooling
setpoint
Note
96 / 176
Siemens
Building Technologies
The default values defined for data point and "Green limit(s)" in the "Device
description" are displayed in the corresponding entry field.
After values are changed (by the user), default values can be regenerated only
by deactivating "Data point monitoring" (with summary checkbox).
7.4.2

Dialog boxes with numeric data points

In numeric data points such as Comfort heating setpoint and Comfort cooling
setpoint, the "Green limits" may depend on neighboring values. Therefore:
To achieve the desired setting range, the data points (heating and cooling
setpoints) and their "Green limits" must be set in relation to the neighboring value.
Dependency of neighboring values always depends on the data point values
(setpoints), not the "Green limits".
Set the heating setpoint by 1 K lower (or max. the same) as the "Green limit"
to display the "Energy indicator" = "Green leaf".
Set the cooling setpoint by 1 K higher (or max. the same) as the "Green limit"
to display the "Energy indicator" = "Green leaf".