Time ratios
Web Server start value
Notes
Exemption from liability
Siemens
Building Technologies
The following time ratios apply to meter replacement:
· It last up to 8 hours from the time the meter (as defined above) is replaced until
the information is available on a consistent basis on the QAX9...
· The following midnight (12:00 am) OZW772... automatically re-generates all
devices where it has detected a meter replacement.
· You must also wait 8 hours after meter replacement when generated manually.
· The following information is available immediately for Synco 700 controllers.
· After writing S-Mode data points with ETS, the device web page for OZW772...
must be generated or updated.
· The OZW772... detects the meter replacement during the daily reading
between 5 and 10 am.
The Web Server maps the Web Server start value as soon as it receives the first
meter value after generating the Synco device.
· The Web Server start value is not the same as the start value for the meter
available on the QAX9...
· An initial generation also occurs when the Synco device is hidden and then
shown after using generate. The reason for the exception is that hiding Synco
devices with meters is backed up using meter replacement. Otherwise, meters
relevant to allocations can unintentionally disappear from the consumption data
file.
The Siemens system for transmitting acquired consumption data for meters uses
the latest technology and security standards. The value as displayed on the meter
applies for allocation purposes in the event of differences between the displayed
value on the meter and the value as transmitted.
6.3

Send consumption data file

Settings are available under: Home > 0.2.150 OZW772.xx > Settings >
Consumption data > Receiver > E-mail receiver 1...2
To set, see Section 2.5.3.6 "Consumption data".
Information on the e-mail outline is available in section 8.2.
Information on outline and content of the appended consumption data file is
available in Section 6.1.
Web server OZW772... V6.0
Record consumption data
79 / 176