Trend

2 e-mail receivers can be defined for the trend function. Each of the 4 trend
channels can send its information at the defined interval to one or both e-mail
receivers. The settings is at:
Path: Home > 0.2.150 OZW772.xx > Settings > Trend
A description is available in Section 9.3, "Send trend data by e-mail".
2.5.3.9

Faults

Enter these settings if the Web Server is to send an e-mail for a fault.
Path: Home > 0.2.150 OZW772.xx > Settings > Faults
Data point
Delete history
Default value: No
Setting values:No,
Yes
Data point
Message triggering
Default val.:
Coming
Setting val:
Coming,
Coming and going
"Local" faults refer to Web Server faults.
Data point
Message triggering
Default val: Coming
Setting val: Coming,
Coming and going
Data point
Message triggering
Default val.:
Coming
Setting val:
Coming,
Coming and
going
"System" faults refer to faults to the KNX device received via the KNX bus.
Web server OZW772... V6.0
Commissioning
Explanation, example
Deletes the history of all events and messages.
: Setting value Yes is a temporary state,
Note
after approximately 2 seconds, the setting value
returns automatically to No.
Explanation, example
Coming: A message is triggered when a fault
is received (start of fault).
Coming and going: A corresponding
message is triggered at start and end of fault.
A Web Server fault displays the LED
Explanation, example
Coming: a message is triggered when a fault is
received (start of fault).
Coming and going: A corresponding message
is triggered at start and end of fault. A Web
Server fault displays the LED
Explanation, example
Coming: A message is triggered when a fault is
received (start of fault).
Coming and going: A corresponding message
is triggered at start and end of fault.
This "Message triggering" impacts faults for
devices on the KNX network (System) that are
included on the Web Server device list.
A fault to Synco devices is displayed with the
LED
.
.
.