Note
Copy trend definition
within OZW
136 / 176
Siemens
Building Technologies
The field turns orange if the selected data point address is unavailable. The
data point address must be corrected to a valid value prior to confirmation.
13. Click OK to confirm.
14. The Save window opens with another warning that the previous trend data
of the trend channel is deleted.
15. Click OK to confirm the action.
Trend data is imported and the trend goes to the defined state as per the imported
file:
– A trend exported in the state "Running" is started automatically after the import
is completed, as long as bus load does not exceed 100%.
– A trend exported in state "Completed", is not started after import.
Only trend definitions of version V2.0 can be imported.
A trend definition can be copied as follows within the same OZW:
1. Export trend definition for the desired trend channel.
2. Import trend definition to another trend channel.
Web server OZW772... V6.0