Additional Settings - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Test e-mail receiver
consumption data
Note
Hide devices
Note
Note
Delete history
Note
Siemens
Building Technologies
Path: Home > 0.2.150 OZW772.xx > Settings > Consumption data > Receiver
Do the test if the Web Server sends consumption data via e-mail.
Data point
Test receiver
Default val: ---
Setting val: ---, Trigger
Consumption data sent
Display val: ---, Yes, No
Cause
Display val:
---, Network cable, DNS setting,
Address mail server, Port
number mail server, E-mail
address receiver, Authentication
mail server.
2.8

Additional settings

You can determine whether a device in the device list can be operated under
"Home".
You can only hide devices on the "Administrator" user level.
Procedure:
1.
Select "Device web pages"
2.
Select
the device you want to hide.
3.
Click [ Hide ]
Click [ Generate ] again to show the device. This may have an impact on the
display of any existing meters in the consumption data file (For details see Section
6.2, Sections replace meter and section Start value Web Server).
Path: Home > 0.2.150 OZW772.xx > Settings > Faults
We recommend deleting the history after you have completed commissioning.
The workflow is described in Section 2.5.3.9, "Faults".
Web server OZW772... V6.0
Commissioning
Explanation, example
"Test receiver" tests the connected to the
selected receiver.
The display changes after a few seconds from
"
" to
---
Yes: Message sent successfully.
No:
Message receiver not reached.
"Cause" displays the results of "Test receiver".
For "Yes" the cause is "---"
For "No" the cause is displayed.
The first fault is displayed for multiple faults.
41 / 176
CE1C5701en
2015-10-12