ABB i-bus EIB Product Manual page 42

Dim actuator modules for the room controller, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
Object: "Slave active/inactive": 1 Bit (EIS1)
The slave mode can be activated ("1") and deactivated ("0") via this object.
On activation/deactivation of the slave mode (e.g. by an OFF command), the
device reports the new switching state.
Object: "Slave brightness value": 1 Byte (EIS6)
The dimmer receives a brightness value from a higher-order lighting control
function via this object.
Object: "Permanent ON": 1 Bit (EIS1)
If this object receives the value "1", the lighting is permanently switched on
at the parameterised brightness value. On receipt of the telegram value "0",
the staircase lighting remains switching on and the dimming down time is
started.
Note: A permanent ON function can also be carried out via the 2-bit object
"Priority / forced operation". The difference is that the lighting is switched off
under certain conditions when the priority is deactivated.
Object: "Duration of staircase lighting": 2 Byte (EIS10)
This object is visible if "yes" has been selected in the parameter "Duration of
staircase lighting can be changed by object".
The staircase lighting time t
seconds. After bus voltage recovery, the object value is overwritten by the
parameterised value.
Object: "Warning stairc. lighting": 1 Bit (EIS1)
If the "Staircase lighting function" has been set in the parameters, this object
can be enabled via a parameter. The object receives the value "1" during the
warning period before the end of the staircase lighting time. The user can
thus be warned e.g. by triggering a push button LED.
Object: "8-bit scene": 1 Bit (EIS1)
The device receives a scene number (1...64) via this object as well as the
information about whether a scene should be retrieved or the current
brightness should be stored in the scene.
Bitwise telegram code:
M:
0 – Scene is retrieved
1 – Scene is stored
x:
Not used
S:
Number of the scene (1...64)
Object value
decimal
hexadecimal
00 or 64
00h or 40h
01 or 65
01h or 41h
02 or 66
02h or 42h
...
...
63 or 127
3Fh or 7Fh
128 or 192
80h or B0h
129 or 193
81h or B1h
130 or 194
82h or B2h
...
...
191 or 255
AFh or FFh
Object: "Disable": 1 Bit (EIS1)
This object is used to disable the output in order to prevent unwanted
operation.
can be set via this object. The time is given in
ON
MxSSSSSS
(MSB)
(LSB)
Meaning
Retrieve scene 1
Retrieve scene 2
Retrieve scene 3
...
Retrieve scene 64
Set scene 1
Set scene 2
Set scene 3
...
Set scene 64
42