5.3
Capacitor Module
5.3
5.3.1
Description
Capacitor modules are used to increase the DC link capacitance to bridge momentary power
losses.
Capacitor modules are connected to the DC link voltage via the integrated DC link busbars.
Capacitor modules function autonomously.
Several capacitor modules can be operated in parallel.
5.3.2
Safety Information
Danger
Risk of electric shock. A hazardous voltage is present for up to 5 minutes after the supply
has been disconnected.
The protective cover may only be opened after this time has expired.
Warning
When opening the protective cover for the DC link, you must activate the release. A suitable
tool (e.g. screwdriver) must be used for this purpose.
The components must only be operated when the protective cover of the DC link is closed.
Damaged components must not be used, otherwise this could result in secondary damage
or accidents.
Caution
The DC link discharge voltage hazard warning must be affixed to the modules in the local
language.
A set of labels in 16 languages is available using Order No.: 6SL3166-3AB00-0AAx.
Notice
The 80 mm clearances above and below the components must be observed.
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
DC link components Booksize
5.3 Capacitor Module
5-13