Cabinet Configuration and EMC Booksize
8.2 Selection of devices required for operation of SINAMICS
Table 8-2
Requirements regarding line fuses and circuit-breakers for Active Line Modules
16 kW
I
fuse
35 A
rated
I
0.2s
>180 A
fuse
I
4s
>130 A
fuse
I
10 s
>100 A
fuse
I
240 s
>60 A
fuse
Table 8-3
Requirements regarding line fuses and circuit-breakers for Smart Line Modules
I
fuse
rated
I
0.2s
fuse
I
4s
fuse
I
10 s
fuse
I
240 s
fuse
See catalog D21.2.
8.2.4
Line contactors
Line contactors are required to provide electrical isolation between the drive line-up and the
line supply.
When selecting a line contactor, the characteristic values in the technical data apply. The
cable routing, the bundling factor and the factor for the ambient temperature according to
EN 60204-1 must be taken into account when dimensioning the various cables.
Caution
Line contactors must not be switched under load.
When the digital output is used to control the line contactor, its making/breaking capacity
must be taken into account.
8-4
36 kW
80 A
>360 A
>260 A
>200 A
>135 A
5 kW
16 A
>70 A
>50 A
>42 A
>30 A
55 kW
125 A
>450 A
>350 A
>250 A
>200 A
10 kW
35 A
>100 A
>80 A
>65 A
>45 A
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
80 kW
160A
>650 A
>505 A
>360 A
>280 A
16 kW
35 A
>180 A
>130 A
>100 A
>60 A
Equipment Manual for Booksize Power Units
120 KW
250A
>865 A
>675 A
>480 A
>380 A
36 kW
80 A
>360 A
>260 A
>200 A
>135 A