Line Connection Booksize
2.3 Basic Line Filter for Active Line Modules
2.3.3.2
Line/load connection
Table 2-2
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Basic Line Filter for Active Line Modules
16 kW
36 kW
55 kW
1) for ring cable lugs to DIN 46234
2-6
Designations
L1, L2, L3, PE
L1´, L2´, L3´, PE
Screw terminal: 10 mm
3-pin/1.5 Nm (see Screw Terminals)
2
PE connection: M6/3 Nm
Screw terminal: 35 mm
2
PE connection: M6/3 Nm
Screw terminal: 50 mm
2
PE connection: M6/3 Nm
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
1)
1)
1)
Equipment Manual for Booksize Power Units