Power Loss Of Components In Rated Operation - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Configuration and EMC Booksize
8.7 Information about cabinet cooling
8.7.3

Power loss of components in rated operation

The following table shows the power loss for components with internal air cooling. The
characteristic values apply for the following conditions:
• Line voltage for Line Modules 400 V
• Pulse frequency of the Motor Modules 4 kHz
• Rated pulse frequency of the Active Line Modules 8 kHz
• Operating components at their rated power
Table 8-14
Control Units and Option Boards
CU320
TB30
CBC10
CBE20
Basic Line Filter for Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Wideband Line Filter for Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Wideband Line Filter for Smart Line Modules
5 kW
10 kW
16 kW
36 kW
Line reactors for Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Line reactors for Smart Line Modules
5 kW
10 kW
16 kW
36 kW
8-38
Overview of power losses
Unit
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
Power loss
20
< 3
< 3
2.8
16
28
41
48
95
70
90
110
150
200
5
9
16
28
170
250
350
450
590
62
116
110
170