X1 Line Connection - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
3.2 Active Line Modules with Internal Air Cooling
3.2.3.3

X1 line connection

Table 3-1
Terminal block X1 Active Line Module 16 kW
Terminal
U1
V1
W1
PE connection
1 for ring cable lugs to DIN 46234
Table 3-2
Terminal block for the Active Line Module (36 kW to 120 kW)
1 for ring cable lugs to DIN 46234
3-8
Technical data
Max. connectable cross-section: 10 mm
Type: Screw terminal 6 (see Connection Methods)
Tightening torque: 1.5 - 1.8 Nm
Threaded hole M5/3 Nm
Terminals
U1
V1
W1
PE connection
1
Technical data
Max. connection voltage:
3-ph. 480 V AC +10% at 47 Hz to 63 Hz
36kW:
Threaded bolt M6/6 Nm
55 kW:
Threaded bolt M8/13 Nm
80 kW to 120 kW:
Threaded bolt M8/13 Nm
36kW:
Threaded hole M6/6 Nm
55 kW:
Threaded hole M6/6 Nm
80 kW to 120 kW:
Threaded hole M8/13 Nm