Braking Module In Booksize Format; Additional Modules; Control Supply Module - Siemens Sinamics S120 Comissioning Manual

With startdrive
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Diagnostics
5.2 Diagnostics using LEDs
5.2.2.7

Braking Module in booksize format

Table 5- 10
Meaning of the LEDs on the Braking Module booksize
LED
Color
State
READY
Off
Green
Continuous
light
Red
Continuous
light
DC LINK
Off
Green
Flashing
light
5.2.3

Additional modules

5.2.3.1

Control Supply Module

Table 5- 11
Control Supply Module – description of the LEDs
LED
Color
State
READY
off
Green
Continuous
light
DC LINK
off
Orange
Continuous
light
Red
Continuous
light
146
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
Component deactivated via terminal.
Component is ready to operate.
Enable signal missing (input terminal)
Overtemperature
Overcurrent trip
I
t monitoring responded
2
Ground fault/short circuit
Note:
In the event of an overtemperature, the error cannot be
acknowledged until after a cooling down time.
There is no DC link voltage or the electronic power supply is
missing or outside permissible tolerance range.
Component not active.
Component active (DC link discharge via braking resistor in
progress).
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
Component is ready to operate.
Electronic power supply is missing or outside permissible
tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Remedy
Diagnose fault (via
output terminals) and
acknowledge it (via
input terminal)
Remedy
Commissioning with Startdrive

Advertisement

Table of Contents
loading