Online Connection Via Profinet Interface; Using The Profinet Io Interface - Siemens Sinamics S120 Comissioning Manual

With startdrive
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Commissioning
4.4 Establishing an online connection to the drive
5. Select one of the following search options in the "Select target device" drop-down list:
– Show devices with the same addresses
– Show all compatible nodes
– Displaying accessible nodes
6. In order to search for the drive device with the set parameters, then click on "Start
search".
The devices that are found are displayed in the table of results.
7. Select your drive device from the table.
8. To establish an online connection to the drive device, click on "Connect".
Result
An online connection has been established between the PG/PC and the drive unit. The
settings are used automatically the next time you go online and the "Go online" dialog is no
longer displayed.
4.4.3

Online connection via PROFINET interface

4.4.3.1

Using the PROFINET IO interface

Establishing an online connection between the PG/PC and the drive unit via a PROFINET interface
The PROFINET interface of the CU320-2 PN is the X150. The drive and PG/PC must be
located in the same subnet in order to establish an online connection. Correspondingly, you
must select the IP address and subnet mask.
To establish an online connection between a PG/PC and an individual drive, proceed as
follows:
1. Search for a device using the online access
2. Assign the device an IP address and device name.
3. Adapt the IP address and subnet mask of the configured device in the project.
4. Compare the assigned interface data with the configured interface data.
94
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0