Online Connection Via Profinet Interface; Establishing An Online Connection Between A Drive And A Pg/Pc - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
5.4 Establishing an online connection to the drive
8. Select your drive unit from the table.
9. To establish an online connection to the drive unit, click "Connect".
The online connection between the PG/PC and the drive unit is established.
The settings are used automatically the next time you go online and the "Go online" dialog is no
longer displayed.
Quick search via "Online access"
In order to obtain a fast overview, you can start a search in "Online access" at the required
interface. If the wiring to your drive is error-free and you have wired the correct drive (LED
flashing for checking), the drive is displayed with the appropriate IP address.
Figure 5-2
5.4.3

Online connection via PROFINET interface

5.4.3.1

Establishing an online connection between a drive and a PG/PC

Overview
The PROFINET communication between a drive and a PG/PC is accomplished via the PROFINET
interface X150. To establish an online connection between a drive and a PG/PC, the drive and PG/
PC must be located in the same subnet. The IP address and subnet mask must be selected or
adapted accordingly.
Requirements
• The drive and PG/PC are located in the same subnet.
Procedure
To establish an online connection between a PG/PC and a drive, proceed as follows:
1. Search for a device via "Online access".
2. Assign the device an IP address and device name.
3. Adapt the IP address and subnet mask of the configured device in the project.
4. Compare the assigned interface data with the configured interface data.
158
Example: Online access
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2