Commissioning
5.7 Basic parameterization of the drive objects
Effects during device replacement
The settings serve to protect confidential company know-how on configuration and
parameterization and limit the end user's possibilities as follows, according to the selected
setting:
• Know-how protection without copy protection
Despite activated know-how protection, the end user can copy the drive settings and transfer
them to further Control Units using any memory card.
• Know-how protection with basic copy protection
Know-how protection is bound to the serial number of the Siemens memory card. When
know-how protection is activated, the know-how-protected drive settings are protected
against copying and use on other memory cards.
Note
After a device replacement, the converter can be operated with the Siemens memory card
from the defective device without knowing the know-how protection password.
• Know-how protection with extended copy protection
Know-how protection is bound to the serial number of the Siemens memory card and the
Control Unit. When know-how protection is activated, the know-how-protected drive
settings are protected against copying and use on other memory cards and Control Units.
Note
After a device replacement, the converter can be operated with the Siemens memory card
from the defective device only if the know-how protection password is known.
Effects on parameters and functions
The following table provides a detailed overview of the effects of the individual protection
settings on parameters and functions with activated know-how protection:
Affected
Protection set‐
tings
Adjustable pa‐
Readable,
rameters
changeable
Readable
192
Adjustable parameters without know-how protection (p...) can be read and changed
when know-how protection is active. You can find a list of the adjustable parameters that
can be read and changed in the SINAMICS S120/S150 List Manual in the chapter "Pa‐
rameters with "KHP_WRITE_NO_LOCK"".
Note:
Adjustable parameters without know-how protection cannot be added to an exception
list (see Chapter "Managing the exception list (Page 197)").
Certain adjustable parameters with know-how protection (p...) can be read but not
changed when know-how protection is active. You can find a list of the adjustable pa‐
rameters that can be read in the SINAMICS S120/S150 List Manual in the chapter "Pa‐
rameters with "KHP_ACTIVE_READ"".
Description
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2