Affected
Protection set‐
tings
Functions
Locked
Executable
Optionally exe‐
cutable
Parameters (see SINAMICS S120/S150 List Manual)
• r7760.0...12
• p7765
• p7766[0...29]
• p7767[0...29]
• p7768[0...29]
5.7.1.12
Configuring know-how protection
Overview
Know-how protection can only be activated and configured in online mode. Therefore, always
make sure that there is an online connection to your drive unit before calling the configuration
screen for know-how protection.
More information on the individual protection settings can be found in Chapter "Know-how
protection (Page 189)".
Requirements
• A SINAMICS S120 control module has been inserted in the device configuration.
• An online connection to the drive has been established.
• Write and know-how protection are disabled.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
The following functions are locked when know-how protection is activated:
•
Loading drive settings into the project (function: "Upload from device")
•
Automatic controller optimization
•
Stationary or rotating measurement of the motor data identification
•
Deleting alarm history and fault history
•
Generating acceptance documents for safety functions
The following functions can be executed when know-how protection is activated:
•
Restoring factory settings
•
Acknowledging faults
•
Displaying faults, alarms, fault history and alarm history
•
Reading out the diagnostic buffer
•
Controlling the drive via the control panel
•
Displaying acceptance documents for safety functions
The following functions can be executed if the "Allow diagnostic functions" option is
enabled when know-how protection is activated:
•
Trace function
•
Measurement function
Write protection/know-how protection status
Know-how protection configuration
Know-how protection password input
Know-how protection password new
Know-how protection password confirmation
5.7 Basic parameterization of the drive objects
Description
Commissioning
193