Commissioning
5.9 Commissioning a drive
Deactivating the control panel
Proceed as follows to return the master control:
1. Click the "Off" button to switch off the drive.
2. Click the "Deactivate" button at "Master control".
The "Deactivate master control" message window opens.
3. Click "Yes" to disable the master control.
The master control is deactivated.
Setting drive enable signals
To set the required enable signals for the control panel, proceed as follows:
1. Click "Set" at "Drive enable signals".
Further areas of the control panel are activated.
2. Click "Acknowledge faults" to acknowledge currently pending faults.
Resetting drive enable signals
To reset unneeded drive enable signals, click on the "Reset" button under "Drive enable signals".
Result
• You are able to traverse the drive with the control panel.
• Enable signals and faults are displayed at "Drive status".
• In addition to "Active fault", the currently pending fault is displayed.
5.9.2

Run the drive

Overview
After you have set the drive enable signals, in the "Control Panel" screen form specify the
operating mode and switch on the motor.
246
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2