5. Select a desired filter in the "Output filter" drop-down list.
Additional display or input fields are now unhidden depending on the respective filter
selected.
6. Now parameterize the associated detailed settings for the selected filter.
You have performed the detail settings for a selected Power Module or Motor Module.
5.3.6.5

Copying and inserting Motor Modules

Overview
In a project with SINAMICS S120 drives, Motor Modules can be copied and inserted within the
same drive or in another drive of the same type. As a consequence, it is only necessary to
configure a Motor Module once.
You copy and insert Motor Modules in the following areas of the project view:
• Project tree
• Device view
DRIVE-CLiQ interconnection
When Motor Modules are inserted, they are automatically wired according to DRIVE-CLiQ
interconnection rules. The settings of the copy source are applied.
Requirements
• A SINAMICS S120 Control Unit has been inserted in the device configuration.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
NOTICE
Damage to a sine-wave filter through incorrect parameter assignment
If a sine-wave filter is installed in your hardware configuration, the sine-wave filter can be
destroyed if it has not been set in the additional data of the Motor Module or Power Module.
• Set the installed sine-wave filter in the "Output filter" drop-down list and add the required
filter parameter data.
Commissioning
5.3 Creating a project offline
131