Parameter Values (For Experts) - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

After the basic parameterization and subsequent download, the "Stationary measurement"
measurement type is active as the "Calculation of motor/control parameters" has already been
performed.
You perform the configuration of the motor data identification in the following steps:
Activating the infeed unit
Click the "1" icon in the "Infeed" area to switch on the infeed unit.
Setting drive enable signals
To set the drive enable signals, click "Set" in the "Drive enable signals" area.
Switch on motor
Click the "1" icon in the "Switch on" area to switch on the motor.
Start measurement
Click "Activate" in the "Measurement" area to start the measurement.
A status display at the center of the screen form shows how the measurement is progressing
(r0047).
The measurement ends automatically, and the message appears that the drive is in the switch-
on inhibited state.
After the measurement, the new parameter values are displayed in the results table. You can
view and check the new values.
Checking measurement results
Check the values that have been determined to ensure that they are plausible. If the values do
not seem appropriate, carry out another measurement.
Close measurement
If you do not want to carry out any further measurements, click the "0" icon in the motor and
infeed area. Then click "Deactivate" under "Master control".
5.9.5.1

Parameter values (for experts)

Overview
You will find the mandatory entries for the measurements depending on the type of drive. The
results of the respective measurements are displayed in the "Stationary/rotating measurement"
screen form after completion of the respective measurement.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Commissioning
5.9 Commissioning a drive
259