Additional Modules; Control Supply Module; Smc10/Smc20 Sensor Module Cabinet - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.1.3

Additional modules

6.1.3.1

Control Supply Module

Table 6-25
Control Supply Module – description of the LEDs
LED
Color
READY
Green
DC LINK
Orange
Red
6.1.3.2

SMC10/SMC20 Sensor Module Cabinet

Table 6-26
Sensor Module Cabinet 10/20 (SMC10/SMC20) – description of the LEDs
LED
Color
RDY
READY
Green
Orange
Red
Green/red
Green/
orange
or
Red/
orange
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
State
Description, cause
off
Electronic power supply is missing or outside permissible tol‐
erance range.
Continu‐
Component is ready to operate.
ous light
off
Electronic power supply is missing or outside permissible tol‐
erance range.
Continu‐
DC link voltage within permissible tolerance range.
ous light
Continu‐
DC link voltage outside permissible tolerance range.
ous light
State
Description, cause
off
Electronic power supply is missing or outside permissible tol‐
erance range.
Continu‐
The component is ready for operation and cyclic DRIVE-CLiQ
ous light
communication is taking place.
Continu‐
DRIVE-CLiQ communication is being established.
ous light
Continu‐
At least one fault is present in this component.
ous light
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Flashing
Firmware is being downloaded.
light 0.5
Hz
Flashing
Firmware download is complete. Wait for POWER ON
light 2 Hz
Flashing
Component recognition via LED is activated (p0144).
light
Note:
Both options depend on the LED status when module recog‐
nition is activated via p0144 = 1.
Diagnostics
6.1 Diagnostics using LEDs
Remedy
Remedy
Remedy and acknowl‐
edge fault
Carry out a POWER ON
299

Advertisement