Requirements
• A SINAMICS S120 CU320-2 PN Control Unit is inserted in the device configuration.
• Insert an Active, Basic or Smart Line Module in the device configuration.
Restrictions
• The use of a Line Module excludes the use of a PM 240-2 Power Module in a drive
configuration.
Important notes
Carefully observe and comply with the following notes before you insert an infeed unit
(placeholder) into the device configuration.
Standard
Generally, the infeed is inserted while configuring directly after the drive in the device view. In
this case, the infeed unit is automatically wired to the drive via the default interface X100.
Exception
If you insert the infeed unit at a later point in time (e.g. after the Motor Module), then the infeed
unit is not automatically connected to the drive. In this case, the default interface X100 provided
for the infeed unit is already assigned. Thus the device configuration must be changed manually.
The following options are available to manually change the device configuration:
• You manually wire the infeed unit to a free interface (see Chapter "Editing DRIVE-CLiQ
connections (Page 117)").
• You change the wiring of the drive object that is currently linked to the X100 interface of the
drive to a different interface. This is automatically linked to the X100 interface when the
infeed unit is inserted.
Procedure
To insert a non-specified infeed unit, proceed as follows:
1. Open "Line Modules" in the hardware catalog.
2. Select an infeed unit in the hardware catalog.
3. Drag and drop the infeed unit into the device view.
The component is automatically interconnected with the CU via DRIVE-CLiQ.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Commissioning
5.3 Creating a project offline
111