3.5

Connecting Racks

To use additional expansion racks, connect additional racks to the existing rack (base rack or
expansion rack).
WARNING
CAUTION
■ Confirming components
Confirm that all components of the connection kit that need to be supplied with an expansion rack
have been delivered (see the table below).
Component name
Upper mounting fixture
Lower mounting fixture
Shield rubber for connection
M12 bolt
M8 bolt
Also, prepare the necessary tools:
・Phillips screwdrivers (No. 2 and No. 3 bits)
・Hexagon wrenches (M8 bolts: Socket size 13; M12 bolts: Socket size 19)
Also, prepare a stepladder because some of the work will need to be performed at height.
86
・ To prevent equipment damage and electric shock, turn off the power to the server
and peripherals and disconnect the power cables from the outlet before
connecting racks.
・ To prevent injury, ensure that at least two persons perform the rack connection
work.
・ You may get on a stepladder when working on the upper part of the rack. Be
careful not to fall from the stepladder.
・ Do not put your foot on the racks when connecting racks.
Quantity
Remarks
1
2
2
4
For upper connection
4
For lower connection