Primary/Reserve Power Cabinet Hardware - Toshiba Strara CTX Series Installation And Maintenance Manual

Digital business telephone systems
Table of Contents

Advertisement

Table 1-26
CTX670 Reserve Power Characteristics
Battery Charger Characteristics
Charger: current limiting
Nominal float voltage: 2.275 volts/cell
Charge current: 0.7 amps maximum
Battery discharge cut-off voltage: 20.5
Table 1-27
CTX670 Typical Reserve Power Duration Estimates
Number of Cabinets
Estimated operation time
Two-battery configuration
Estimated operation time
Four-battery configuration
DC Current Drain
(-24VDC)
1. Assumes 80 ampere-hours with 12VDC batteries.

Primary/Reserve Power Cabinet Hardware

The type of cabinet mounting can have an effect the power requirements. There are two types of
mounting for the CTX100 and CTX670 (listed below).
Cabinet Wall Mounting – The lightweight and compact design of CTX100 and CTX670 enables
easy wall mounting. Wall Mounting requires no special hardware.
Cabinet Floor Mounting – Only the CTX670 can be floor mounted (requires the BFIF hardware
kit). If floor mounting three or more cabinets, AC and reserve power must be connected to the
BCCB conduit connection box option by a licensed electrician. If more than two cabinets require
reserve power batteries, the BBDB must be installed.
Underwriters' Laboratory (UL) and local electrical codes require certain standards for connecting
commercial AC and reserve power to the Strata CTX system.
assemblies may be required to meet UL and local electrical code standards.
The power distribution hardware for the CTX100 is shown in
Table 1-28
CTX100 Cabinet Power Distribution Hardware
Option
Strata CTX100 cabinet power supply is supplied with each cabinet. Operates with 240VAC as
the system's primary power source and requires 1.8 amps AC per cabinet.
APSU112
The power supply AC cord is 152.4 cm (5 ft.) long with a standard three prong plug.
A three-meter long battery cable is used to connect reserve power batteries to the ABCS
ABTC-3M
battery charger when the system has less than three cabinets. One reserve power cable is
required for each cabinet.
Option battery charger that is installed on the APSU112 power supply. One per cabinet is
required with the ABTC-3M if connecting reserve power batteries to the CTX100.
ABCS
Note
Strata CTX I&M September 2002
1 cabinet
2 cabinets
3 cabinets
±
4 cabinets
0.5VDC
1
2
12.0 hr.
6.0 hr.
24.0 hr.
12.0 hr.
4.6
8.7
amps.
amps.
ABCS is built in on UK & European products.
Maximum Battery Charger Drain (-24VDC)
6.0 amps
5 cabinets
12.0 amps
6 cabinets
18.0 amps
7 cabinets
24.0 amps
1
3
4
4.0 hr.
3.0 hr.
8.0 hr.
6.0 hr.
12.8
16.9
amps.
amps.
Tables 1-26
Table
1-28.
Description
Strata CTX Configuration
30.0 amps
36.0 amps
42.0 amps
5
6
2.5 hr.
2.0 hr.
5.0 hr.
4.0 hr.
21.0
25.1
amps.
amps.
and
1-29
describe which
7
1.8 hr.
3.5 hr.
29.2
amps.
1-33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Strara ctx100Strara ctx670

Table of Contents