Line Modules
5.5 Active Line Modules Chassis-2
5.5.6

Electrical connection

Attaching the PE connections
The 3 PE connections must be attached before installing the Active Line Module. The
connecting busbars are included in the accessory pack.
Secure each PE connection with 2 screws on the Active Line Module, torque 25 Nm.
Figure 5-49
242
Attaching the PE connections
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9