X49 Terminal Block - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

7.3.10

X49 terminal block

Table 7- 8
Max. connectable cross-section: 1.5 mm
The terminal strip is coded at terminal 6; please use the corresponding connector from the accessory
pack.
Note
Function of the "LAMPPWR" signal
By connecting a signal lamp, the "LAMPPWR" terminal can be used in large cabinet groups
for signaling the power unit in which a problem exists. Once there is a fault in the respective
power supply unit, a voltage of 24 V DC is output at the output.
Note: During a firmware update, the output alternates between 0 V and 24 V.
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
Terminal strip X49
Connector
Terminal
1
2
3
4
5
6
Function
Technical specifications
LAMPPWR
Supply voltage: 24 V DC
Max. Load current: 100 mA
M
If the power unit has a fault condition, then
voltage is available at the terminals.
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
NC
Reserved, do not use
2
Motor Modules Chassis-2
7.3 Interface description
301