Siemens SINAMICS S120 Equipment Manual page 378

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor-side power components
9.3 dv/dt filter plus Voltage Peak Limiter
Figure 9-9
Connecting a dv/dt filter with Voltage Peak Limiter for versions with two dv/dt reactors to a Motor Module
Chassis-2
Cable cross-sections
Table 9- 23
dV/dt filter plus voltage
6SL3000-2DE32-6AA0
6SL3000-2DE35-0AA0
6SL3000-2DE38-4AA0
6SL3000-2DE41-4AA0
6SL3000-2DH31-0AA0
6SL3000-2DH31-5AA0
6SL3000-2DH32-2AA0
6SL3000-2DH33-3AA0
6SL3000-2DH34-1AA0
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
6SL3000-2DH41-3AA0
376
Cable cross-sections for connections between the dV/dt filter plus voltage peak limiter
and Motor Module
Connection to the DC link
peak limiter
(DCPS/DCNS)
[mm²]
Line voltage 3 AC 380 ... 480 V
35
70
2 x 50
2 x 120
Line voltage 3 AC 500 ... 690 V
16
16
70
70
120
120
2 x 70
2 x 120
Connection between dV/dt reactor and
voltage peak limiter
(1U2, 1V2, 1W2) [mm²]
10
16
50
120
6
6
16
16
35
35
70
120
Air-cooled chassis power units