Line/Load Connection - Siemens SINAMICS S120 Equipment Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.4.3.3

Line/load connection

Table 5- 31
Line/load connection of the Active Line Module
Terminals
Technical specifications
U1, V1, W1
Voltage:
3 AC power input
Frequency: 47 ... 63 Hz
Connecting thread:
DCPA, DCNA
Voltage:
Connection for Brak-
ing Module
Connections:
DCP, DCN
Voltage:
DC power output
Connections:
PE connection
Connecting thread:
PE1, PE2
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
570 ... 720 V DC
750 ... 1035 V DC
Frame sizes FX / GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HX / JX: Connection for connection clip
570 ... 720 V DC
750 ... 1035 V DC
Frame sizes FX / GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HX / JX: d = 12 mm (M10 / 25 Nm) flat connector for busbar connection
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Line Modules
5.4 Active Line Modules
1)
1)
1)
1)
199

Advertisement