Line Modules
5.2 Basic Line Modules
5.2.3.3
Line/load connection
Table 5- 2
Line/load connection of the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
134
Technical specifications
Voltage:
3 AC 380 V -10% (-15% < 1 min) ... 3 AC 480 V +10%
•
3 AC 500 V -10% (-15% < 1 min) ... 3 AC 690 V +10%
•
Frequency: 47 ... 63 Hz
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Voltage:
513 ... 648 VDC
•
675 ... 932 VDC
•
Connections:
Frame sizes FB, GB, GD: Threaded bolts M6 / 6 Nm for cable lugs according to DIN 46234 /
DIN 46235
1)
Voltage:
513 ... 648 VDC
•
675 ... 932 VDC
•
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
•
1)
1)
1)
Air-cooled chassis power units
Manual, 07/2019, 6SL3097-4AE00-0BP9
1)
1)
1)