Step 8 Align the PDC mounting holes with the expansion bolt holes.
Step 9 Level the cabinet using a level and an adjustable wrench, as shown in
Figure 4-5 Leveling the PDC
(1) Level
Step 10 Partially drive the four M12 expansion bolts into the expansion sleeves.
Step 11 (Optional) Use a torque wrench to tighten the bolts to a torque of 45 N· m in diagonal order, as
shown in
Issue 01 (2016-02-27)
Wrench an anchor bolt clockwise to elevate a cabinet foot, or wrench an anchor bolt anticlockwise to
lower it. The cabinet feet can be adjusted within a range of 0–8 mm.
To prevent cabinet tilting, adjust all the feet at the four corners instead of one foot.
Do not remove anchor bolts, because this work brings you only a great deal of reworking.
Figure
4-6.
Huawei Proprietary and Confidential