PDU8000 Modular Precision Power Distribution Cabinet
User Manual
YJV5 cables are recommended. The conductor working temperature is 90º C, and the ambient
temperature is 40º C.
Table D-1 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)
Issue 01 (2016-02-27)
D
Power Cable Specifications
Table D-1
lists the cable specifications.
Rated
Current
160 A
250 A
400 A
160 A
250 A
400 A
< 10 A
10 A ≤ I ≤ 40
A
40 A < I ≤ 63
A
< 10 A
10 A ≤ I ≤ 40
A
40 A < I ≤ 63
A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cable
Terminal/Bolt
Diameter
Specifications
2
50 mm
DT-M10
2
95 mm
DT-M12
2
185 mm
DT-M12
2
25 mm
DT-M10
2
50 mm
DT-M10
2
150 mm
DT-M12
2
2.5 mm
Cord end
terminal (plug
depth 8–12 mm)
2
6 mm
Cord end
terminal (plug
depth 8–12 mm)
2
10 mm
Cord end
terminal (plug
depth 8–12 mm)
2
2.5 mm
OT-M6
2
6 mm
OT-M6
2
10 mm
OT-M6

D Power Cable Specifications

Recommended
Torque
26–33 N· m
46–58 N· m
46–58 N· m
26–33 N· m
26–33 N· m
46–58 N· m
1.5–1.8 N· m
1.5–1.8 N· m
1.5–1.8 N· m
4.9 N· m
4.9 N· m
4.9 N· m