Installing The Pdc On A Concrete Floor - Huawei PDU8000 User Manual

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual

4.4.1 Installing the PDC on a Concrete Floor

Procedure
Step 1 Determine the PDC installation position based on its application scenario.
Step 2 Mark the positions for installing expansion bolts, as shown in
Figure 4-2 W x D (mm): 600 x 1200
Step 3 Drill holes to depths of 52 mm to 60 mm at positions for installing expansion bolts using a
hammer drill.
Step 4 Slightly tighten the expansion bolt and vertically insert it into the hole. Knock the expansion
bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole.
Step 5 Partially tighten the expansion bolt.
Step 6 Remove the bolt, flat washer, and spring washer.
Issue 01 (2016-02-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide
Figure
4-2.