Figure 4-7 Leveling and tightening bolts
(1) Anchor bolt
Step 5 (Optional) Use a torque wrench to tighten the bolts to a torque of 45 N· m in diagonal order.
----End
4.4.3 (Optional) Combining Cabinets
Procedure
Step 1 Remove the front and rear doors of the PDC and level the PDC, as shown by (1) in
4-8.
Step 2 Remove the cabinet connecting kits from the rack, as shown by (2) in
Step 3 Secure the connecting kits in the connection positions on the front door using screws, as
shown by (3) in
Step 4 Use the same method to secure the connecting plates in the connection positions on the rear
door.
Step 5 Repeat the procedure to combine other PDCs.
Issue 01 (2016-02-27)
Figure
4-8.
A connecting plate is initially secured by one screw. Remove the screw from the column in the
adjacent cabinet to secure a connecting plate.
Ensure that the vertical deviation and the distances between cabinets are within 3 mm after the
cabinets are combined.