Commissioning A Water Sensor; Commissioning A Wlds900 Water Sensor - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 2 Check the monitoring functions of smoke sensor.
Table 5-22 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End

5.5.3 Commissioning a Water Sensor

5.5.3.1 Commissioning a WLDS900 Water Sensor

If a water sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Set water sensor parameters.
1.
2.
3.
4.
5.
6.
7.
Step 2 Check functions of water sensors.
Issue 07 (2020-03-16)
Normal Connection Status
DI1_smoke alarm is displayed
on the active alarm page of the
app or WebUI.
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. The
specific alarm then can be reported.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the water sensor is connected to the AI/DI_1 port on the ECC800.
The default alarm severity of the AI/DI port is Minor. If you want to change the alarm severity, see
How Should I Configure Alarm Parameters.
Log in to the ECC800 WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to ECC800, set Device Name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Leak and click
Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
Set Leak sensor to Enable and click Submit.
Confirm that Leak sensor type is automatically identified as Leak sensor(Rope).
Ensure that Leak power supply is Yes.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
Press the reset button of the
smoke sensor to clear the alarm.
117