Step 3 Choose Settings > Communication, and set IP address assign to Automatic(DHCP).
Step 4 Tap
----End

5.3.2 How to Set and Add a UPS2000-G?

Prerequisites
One end of the straight-through cable has been connected to the COM_1 or COM_2 port on
the Modbus expansion card of the UPS2000-G, and the other end has been connected to the
COM port on the ETH converter.
Procedure
Step 1 Set monitoring parameters for the UPS2000-G.
Table 5-1 Setting a device address
Device
Toggle
Address
Switch 1
1
ON
2
OFF
3
ON
4
OFF
Issue 07 (2020-03-16)
to go back to the main menu screen.
After setting parameters for the integrated UPS, the ECC800 discovers the access from the integrated
UPS automatically.
Set monitoring parameters for the UPS2000-G-(1-3 kVA).
Operate the DIP switch SW1 on the optional Modbus card to set the UPS2000-G device address. Toggle
switches 1 to 8 of DIP switch SW1 specify the device address in binary mode. ON indicates 1, and OFF
indicates 0.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
Set monitoring parameters for the UPS2000-G-(6–20 kVA).
Operate the DIP switch S2 on the optional Modbus card to set the UPS2000-G device address. Toggle
switches 1 to 8 of DIP switch S2 specify the device address in binary mode. ON indicates 0, and OFF
indicates 1.
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
5 Power-On Commissioning
Toggle
Toggle
Switch 6
Switch 7
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Toggle
Switch 8
OFF
OFF
OFF
OFF
87