Pad - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Indicators
Table 3-50 ETH converter indicators
Indicator
PWR
RUN
ALM

3.2.16 Pad

The pad allows the wireless access from the data center management system. You can monitor
the equipment in the data center and environmental parameters in real time over the APP.
Figure 3-30
Issue 07 (2020-03-16)
Color
Name
Green
Power input
status
indicator
Green
Operating
status
indicator
Red
Alarm
indicator
shows a pad.
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The ETH converter
long intervals
successfully registers with the
ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The communication fails or
short
the ETH converter fails to
intervals
register with the ECC800 (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.