8.1.6 How Should I Set and Add Devices?

8.1.6.1 How Should I Set and Add Integrated UPS Parameters?

Prerequisites
One end of the straight-through cable has been connected to the FE port on the integrated
UPS, and the other end has been connected to the POE port on the smart ETH gateway.
Procedure
Step 1 Start the integrated UPS, and tap System Info on the LCD.
Step 2 Choose System Info > Settings, enter the user name admin and password 000001, and then
tap
Step 3 Choose Settings > Communication, and set IP address assign to Automatic(DHCP).
Step 4 Tap
----End

8.1.6.2 How to Set and Add a UPS2000-G?

Prerequisites
One end of the straight-through cable has been connected to the COM_1 or COM_2 port on
the Modbus expansion card of the UPS2000-G, and the other end has been connected to the
COM port on the ETH converter.
Procedure
Step 1 Set monitoring parameters for the UPS2000-G.
Issue 06 (2020-04-22)
. In the displayed dialog box for confirming the password, tap OK.
If you enter incorrect passwords for five consecutive times, you will be locked out for 5 minutes.
to go back to the main menu screen.
After setting parameters for the integrated UPS, the ECC800-Pro discovers the access from the
integrated UPS automatically.
Set monitoring parameters for the UPS2000-G-(1 kVA-3 kVA).
Operate the DIP switch SW1 on the optional Modbus card to set the UPS2000-G device address. Toggle
switches 1 to 8 of DIP switch SW1 specify the device address in binary mode. ON indicates 1, and OFF
indicates 0.